Section 3 - Main Terminal Rooms

Main

Table of Contents

Back

Printer Friendly Version

getacro

  1. The building owner or occupant shall provide a room for network termination and distribution when specified by TELUS Communications Inc. and arrange for all necessary environmental requirements.   The need for a terminating room is dependent on the size and occupancy of the building.
  2. The size of the terminating room is dependent on the anticipated ultimate number of connections and shall be specified by TELUS Communications Inc. for each building project.
  3. Network terminating rooms shall be free of other building services, dry, well ventilated, dust proof and painted a light color.  The floor shall be painted, sealed or covered with tile.
  4. All network terminating rooms shall be well lit  (minimum of 1000 lux at working plane) and equipped with one 110 volt (A.C.) duplex electrical outlet, or as required by TELUS Communications Inc.
  5. The main terminal room must be a separate room if the power voltages exceed 8700V.  Joint power/tel rooms must meet clearance requirements as per C.E.C. 60-404.
  6. Plywood backboards shall be provided as per Section 3 - Plywood Backboards.
  7. No. 6 green insulated A.W.G. ground wire.  See Section 3 - Grounding Requirements