All residential buildings (including mobile homes) require a number
6 Green insulated A.W.G. ground wire (Max 8M) at the location of each
communication circuit protector. The owner/developer is
responsible for providing this number 6 insulated ground and a 25mm
conduit from the TELUS Communications Inc. protector location to the
electrical power panel. The ground wire shall be connected to a
suitable ground electrode and installed in accordance with The
Canadian Electrical Code Part 1.
-
Buildings classified as Office, Commercial, Industrial,
Institutional and Apartments, Townhouses, Row Housing and Condominiums
will require the building owner/developer to supply and install a No.
6 green insulated A.W.G. (max 8M) or larger ground wire as specified
by TELUS Communications Inc. at the location of the communication
network circuit protectors. This ground wire shall be connected
to a suitable building ground electrode and be installed in accordance
with The Canadian Electrical Code, Part 1.