- Plywood backboards for TELUS Communications Inc. shall not be
installed in public areas. See Section
3 - Public Access Cabinets
- The building owner or occupant shall supply and install 19mm plywood
backboards for the mounting of TELUS Communications Inc.'s network
termination equipment. The size of backboard is dependent on the
number of network connections to be made and will be identified by
TELUS Communications Inc. for each building project.
- Plywood backboards shall be attached to the building walls and shall
be capable of supporting a maximum dead weight of 15 lbs/sq. ft. (.1
lbs/sq. in.)
- Backboards shall at all times be readily accessible to TELUS
Communications Inc. personnel, and shall be placed in a location
mutually agreed upon by TELUS Communications Inc. and the
owner/developer. (1m working area must be maintained as per
Canadian Electrical Code Section 2-308)
- No. 6 insulated A.W.G. ground wire. See Section
3 - Grounding Requirements.