- Entrance conduit and main terminal panel sizes for network services
in buildings shall be utilized for TELUS Communications Inc. services
only and sized as follows:
| No. of Units |
U/G Entrance |
Aerial Entrance |
| 5-25 |
50 (2") |
32 (1-1/4" min) |
| 26-50 |
50 (2") |
38 (1-1/2" min) |
| |
|
|
| 51-100 |
100 (4") |
50 (2" min) |
| Greater than 100 - Dependant on cable
requirement. (To be stipulated by TELUS Communications Inc.) |
Main Terminal Panel
| |
METAL CABINET
INSIDE/OUTSIDE
c/w 19mm Mount Backboard |
PLYWOOD BACKBOARD
INSIDE MOUNT |
| No. of Units |
Width |
Length |
Depth |
Width |
Length |
Depth |
| 3-12 |
610mm (24") |
610mm (24") |
152mm (6") |
610mm (24") |
610mm (24") |
19mm (3/4") |
| 13-25 |
610mm (24") |
915mm (36") |
152mm (6") |
762mm (30") |
915mm (36") |
19mm (3/4") |
| 26-50 |
915mm (36") |
915mm (36") |
152mm (6") |
1220mm (48") |
1220mm (48") |
19mm (3/4") |
| 51-100 |
1220mm (48") |
915mm (36") |
152mm (6") |
1220mm (48") |
1220mm (48") |
19mm (3/4") |
- For buildings with more than 100 units where a self contained
terminal room is required, the size of the room is dependent on the
total number of units and the percentage of business occupancy.
The room size will then be specified by TELUS Communications Inc.
- Conduit, manholes and pedestals required on private property for the
distribution of network communication facilities in townhouse, row
housing, condominium and apartment developments shall be of a design
approved by TELUS Communications Inc. For individual project
requirements, contact you local BICS consultant.
- The following data may be used as a guide in determining the type
and size of common requirements for a specified project.
| ITEM |
TYPE |
SIZE |
| Main Duct Runs Between Access Points. (Manholes or
Pull Boxes) |
Rigid PVC or DBII
CSA B 196.3 or 196.1 Spec |
100mm |
| Entrance Duct to Building Panel |
Rigid PVC or DBII
CSA B 196.3 or 196.1 Spec |
50mm and 100mm |
| Pull Box Over 100 Lines |
Concrete
TELUS Communications Inc.
Spec PB-1 |
(W x L x D)
1.22m x 1.22m x 1.22m
1.22m x 1.83m x 1.98m
See Note 5 |
| Externally Mounted Building Cabinets, Fittings and Accessories |
CSA Weatherproof Cabinet or Approved Equivalent |
(Refer to Item #1) |
| Ground at Network Interface |
Copper Insulated |
No. 6 insulated A.W.G. or Larger as Specified by TELUS
Communications Inc. |
Note:
Electrical metallic tubing (E.M.T.) Metallic flexible conduit and
polyethylene tubing (Corlon, etc.) are not approved for network
underground services.
- Specifications for pull boxes and manholes may be obtained from your
local TELUS Communications Inc. BICS consultant.
- TELUS Communications Inc. BICS should be contacted at the
preplanning stage to discuss all conduit requirements.
- Entrance duct(s) to extend within 1m (3') of building panel.
>